When it comes to ensuring seamless power transfer and reliability, the Generac Transfer Switch, Automatic | 400A Non-Service Entrance Rated (RTSC400A3) stands out as a robust and efficient solution. This transfer switch is specifically designed for single-phase generators and offers a range of features that make it an essential addition for maintaining critical power during outages.
| Weight | 133 lbs |
|---|---|
| Dimensions | 10 × 24 × 36 in |
| Service Entrance Rated | No |
| Pre-Wired | No |
| Load Shedding | Built-In |
| Canada Approved | No |
| Whole House | No |
| Single Load | Yes |
| Product Series | RTS Series |
| Rated Amperage | 400 |
| Voltage | 120/240 1phase |
| Load Transition Type (Automatic) | Open Transition |
| Enclosure Type | NEMA 3R |
| Compliance | cETLus |
| Whitstand Rating (Amps) | 22, 000 |
| Lug Range | 600 MCM – #4 or (2) 1/0 – 250 MCM |
| Number of Managable Individual HVACs | 4 (24 VAC Controlled) |
| Utility Voltage Drop-Out | <60% |
| Timer to Generator Start | 10 Seconds Factory Set (Adjustable) |
| Engine Warmup Delay | 5 Seconds |
| Standby Voltage Sensor | 60% for 5 Seconds |
| Utility Voltage Pickup | >80% |
| Re-transfer Time Delay | 15 Seconds |
| Engine Cooldown Timer | 60 Seconds |
| Exerciser | Nexus: 12 Minutes Weekly / Evolution: 5-12 Minutes Adjustable |
| Circuited | No |
| Home Link | No |

A member of our team will be in touch shortly to discuss how we can help to meet your needs.