Power Zone 410 Controller
A 128 x 64 graphical display with full system status, protections, alarm history and NFPA 110 capability.
5-Time #1 Generac Dealer in Canada
Generac 32kW XG Protector (XG03245): 32 kW on natural gas or propane from a 4.5L engine at 1,800 RPM, with a Power Zone 410 controller, cellular Mobile Link and a 5-year / 2,000-hour limited warranty.
Priced per project
Send us your details and we will prepare a quote for your site.
Get a Free Quote Or call 1-844-443-6776The Generac 32kW XG Protector (XG03245) moves up to the 4.5L engine at 1,800 RPM, with a Power Zone 410 controller and cellular Mobile Link as standard. It delivers 32 kW on natural gas or propane.
Best fit: large homes, estates and light commercial sites that have outgrown air-cooled units and want a slower-running 1,800 RPM engine.
A 128 x 64 graphical display with full system status, protections, alarm history and NFPA 110 capability.
Standard cellular connectivity for Mobile Link and Fleet, with status and maintenance information from anywhere.
Regular maintenance points are on one side of the unit, which simplifies service on tighter sites.
Natural gas or propane vapour is selected at the controller.
A corrosion-resistant enclosure and frame, with low-speed exercise at 1,200 RPM and 58 dB(A).
5-year / 2,000-hour limited warranty.
At 120/240V single-phase the 32kW supplies up to 133 amps on either fuel. It is also configurable for 3-phase: 208/120V at 111 A, 240/120V at 96 A and 480/277V at 48 A, using Generac’s field-installable kits for the higher voltage options.
Natural gas use is 6.8 m³/hr at half load and 11.5 m³/hr at full load. Propane use is 12.9 and 18.5 L/hr, so large tanks or a good gas service matter for long outages.
Platinum sizing recommendation: A 32kW is a bigger step than the kW number suggests, because it weighs 1,781 lb (808 kg) and needs the right pad and a delivery plan. We review your loads, fuel and site access before recommending it.
The 32kW shares its enclosure, 1,781 lb (808 kg) weight and 4.5L engine with the 40kW, so the choice between them comes down to your load. It needs a Group 27R, 725 CCA battery, which is not included.
Generator Experts is the generator side of Platinum Electrical Contractors, a licensed Ontario electrical contractor with commercial, industrial and institutional experience since 1991. We size the 32kW for your building, handle commercial generator installation, supply the right transfer switches and concrete generator pads, and keep it ready with maintenance plans and service and repair.
We can confirm whether the 32kW fits your building or whether a smaller or larger Generac liquid-cooled generator would be a better match.
| Weight | 1781 lbs |
|---|---|
| Dimensions | 83.5 × 33.9 × 45.2 in |
| Model | XG03245 |
| Fuel Type | Natural Gas or Liquid Propane |
| Standby Power, Propane (LP) | 32 kW |
| Standby Power, Natural Gas (NG) | 32 kW |
| Max. Continuous Amps at 120/240V 1-Phase (LP / NG) | 133 / 133 |
| Main Line Circuit Breaker (120/240V 1-Phase) | 150 A |
| Voltage Options | 120/240V 1-phase; 120/208V 3-phase; 120/240V 3-phase; 277/480V 3-phase |
| Engine | Generac 4.5L in-line 4-cylinder, naturally aspirated |
| Operating Speed | 1,800 RPM (exercise 1,200 RPM) |
| Crankcase Oil Capacity | 11 L (2.9 US gal) |
| Controller | Power Zone 410 |
| Remote Monitoring | Mobile Link: cellular standard |
| Battery | Group 27R, 725 CCA minimum (12V, not included) |
| Sound at 7 m (23 ft), Exercise Speed | 58 dB(A) |
| Sound at 7 m (23 ft), Operating Speed, No Load | 64 dB(A) |
| Natural Gas Use, 50% Load | 6.8 m³/hr |
| Natural Gas Use, 100% Load | 11.5 m³/hr |
| Propane Use, 50% Load | 12.9 L/hr |
| Propane Use, 100% Load | 18.5 L/hr |
| Fuel Pressure Required | NG 3.5–14 in. WC (0.87–3.48 kPa); LP 7–14 in. WC (1.74–3.48 kPa) |
| Dimensions (L x W x H) | 83.5 x 33.9 x 45.2 in (212.1 x 86.2 x 114.7 cm) |
| Generator Weight | 1,781 lb (808 kg) |
| Minimum Concrete Pad (W x L) | 45.9 x 95.4 in (1,166 x 2,423 mm) |
| Enclosure | Aluminum, sound attenuated |
| Warranty | 5-year / 2,000-hour limited |
| Minimum Distance from Structure | 18 in (457 mm), per local code |